How Does The Pneumatic Actuator of Control Valve Work

How Does The Pneumatic Actuator of Control Valve Work


Pneumatic Control Valve Actuators
Pneumatic actuators are commonly used to actuate control valves and are available in two main forms;
  • Piston actuators
  • Diaphragm actuators
Piston actuators
Piston actuators are generally used where the stroke of a diaphragm actuator would be too short or the thrust is too small. The compressed air is applied to a solid piston contained within a solid cylinder.

Piston actuators can be single acting or double acting, can withstand higher input pressures and can offer smaller cylinder volumes, which can act at high speed.
Piston Actuator Sketch


Diaphragm actuators
Diaphragm actuators have compressed air applied to a flexible membrane called the diaphragm. The below Figure shows a rolling diaphragm where the effective diaphragm area is virtually constant throughout the actuator stroke.
Pneumatic Diaphragm Actuator Sketch
These types of actuators are single acting, in that air is only supplied to one side of the diaphragm, and they can be either direct acting (spring-to-retract) or reverse acting (spring-to-extend), which we also called air to open and air to close. 

Reverse acting (spring-to-extend)
The operating force is given from compressed air pressure, which is applied to a flexible diaphragm. The actuator is designed so that the force resulting from the air pressure, multiplied by the area of the diaphragm, overcomes the force exerted (in the opposite direction) by the spring(s).

The diaphragm (Above Figure) is pushed upwards, pulling the stem up, and if the stem is connected to a direct acting valve, the plug is opened. The actuator is designed so that with a specific change of air pressure, the stem will move sufficiently to move the valve through its complete stroke from fully-closed to fully-open.

As the air pressure decreases, the spring(s) moves the stem in the opposite direction. The range of air pressure is equal to the stated actuator spring rating, for example 0.2 – 1 bar.

With a larger valve and/or a higher differential pressure to work against, more force is needed to reach full valve movement.

To generate more power, a larger diaphragm area or higher spring range is needed. This is why controls manufacturers offer a range of pneumatic actuators to match a range of valves – comprising increasing diaphragm areas, and a choice of spring ranges to create different power forces.

The diagrams in Below Figure show the components of a basic pneumatic actuator and the direction of spindle movement with increasing air pressure.

Direct acting and reverse acting diaphragm actuator

Direct acting actuator (spring-to-retract)
The direct acting actuator is designed with the spring below the diaphragm, having air supplied to the space above the diaphragm. The result, with increasing air pressure, is stem movement in the opposite direction to the reverse acting actuator.

The effect of this movement on the valve opening depends on the design and type of valve used, and is illustrated in Above Figure.

There is however, an alternative, which is shown in Below Figure. A direct acting pneumatic actuator is coupled to a control valve with a reverse acting plug (sometimes called a ‘hanging plug’).

Air to Open Control Valve Sketch

The choice between direct acting and reverse acting pneumatic controls depends on what position the valve should revert to in the event of failure of the compressed air supply. Should the valve close or be wide-open?

This choice depends upon the nature of the application and safety requirements. It makes sense for steam valves to close on air failure, and cooling valves to open on air failure.

The combination of actuator and valve type must be considered.

The below Figures sow the net effect of the various combinations.
Net effect of various combination for two-port valves
Net effect of various combination for three-port valves